AIR HANDLING UNIT
-
AHU With Thermal / Non Thermal break section
-
MOC- GI IN & OUT / S.S. IN & OUT
-
INFILL MATERIAL PUFF - Polyurethane Foam / Rockwool
-
THICKNESS - 25 MM TO 45 MM
-
COLOUR - Offwhite / Blue
-
BLOWER- BACKWARD/ FORWARD/ PLUG TYPE/ EC BLUE
-
COIL - DIRECT EXPANSION/ CHILLED WATER
-
EU3 - Prefilters (85% down to 20 micron)
-
EU4 - Prefilters (90% down to 10 micron)
-
EU7 - Intermediate Filter (99% down to 3 micron)
-
EU12 - HEPA Filter - Supply (99.97% down to 0.3 micron)
-
Marine light (LED) with limit switch across fan sections door shall be provided with switch for marine light on / off outside the unit. Provision for View Glass in the Fan Section.
-
Opposed blade low leakage extruded aluminum volume control dampers For Supply , return air & fresh Air will be Provided.
-
Sandwitch type 13 mm thick nitrile rubber Insulated SS 304 drain pan.
-
Filters shall be flanged type & filter face velocity not to exceed 500 FPM.
![]() | ![]() |
---|---|
![]() | ![]() |